Specifications Table for FDA-A / RZA-D

FDA200AXVEB / RZA200D7Y1B FDA250AXVEB / RZA250D7Y1B
Cooling capacity Nom. kW 19.0 (1) 22.0 (1)
Heating capacity Nom. kW 22.4 (2) 24.0 (2)
Space cooling Capacity Pdesign kW 19.0 22.0
  SEER   6.26 5.38
  ηs,c % 247 212
  Annual energy consumption kWh/a 1,821 2,455
  A Condition (35°C - 27/19) Pdc kW 19.0 22.0
    EERd   2.69 2.51
    Power input kW 7.06 8.76
  B Condition (30°C - 27/19) Pdc kW 14.1 16.2
    EERd   5.28 4.46
    Power input kW 2.66 3.63
  C Condition (25°C - 27/19) Pdc kW 8.93 10.4
    EERd   8.89 7.22
    Power input kW 1.00 1.44
  D Condition (20°C - 27/19) Pdc kW 4.66 4.60
    EERd   8.51 6.92
    Power input kW 0.55 0.67
Space heating (Average climate) Capacity Pdesign kW 11.2 12.1
  SCOP/A   3.59 3.55
  SCOPnet/A   3.59 3.55
  ηs,h % 141 139
  Annual energy consumption kWh/a 4,368 4,765
  Required back up heating cap at design conditions kW 0.00 0.00
  TOL Tol (temperature operating limit) °C -10 -10
    Pdh (declared heating cap) kW 11.2 12.1
    COPd (declared COP)   2.20 2.18
    Power input kW 5.08 5.55
  TBivalent Tbiv (bivalent temperature) °C -10 -10
    Pdh (declared heating cap) kW 11.2 12.1
    COPd (declared COP)   2.20 2.18
    Power input kW 5.08 5.55
  A Condition (-7°C) Pdh (declared heating cap) kW 9.86 10.7
    COPd (declared COP)   2.40 2.43
    Power input kW 4.11 4.41
  B Condition (2°C) Pdh (declared heating cap) kW 6.05 6.52
    COPd (declared COP)   3.39 3.39
    Power input kW 1.78 1.92
  C Condition (7°C) Pdh (declared heating cap) kW 3.92 4.19
    COPd (declared COP)   5.04 4.84
    Power input kW 0.78 0.87
  D Condition (12°C) Pdh (declared heating cap) kW 3.75 3.82
    COPd (declared COP)   5.28 5.05
    Power input kW 0.71 0.76
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW 0.031 0.031
    Heating PCK kW 0.031 0.031
  Off mode Cooling POFF kW 0.031 0.031
    Heating POFF kW 0.040 0.040
  Standby mode Cooling PSB kW 0.031 0.031
    Heating PSB kW 0.040 0.040
  Thermostat-off mode Cooling PTO kW 0.018 0.018
    Heating PTO kW 0.052 0.052
Indication if the heater is equipped with a supplementary heater (pair application) No No
Supplementary heater (pair application) Back-up capacity Heating elbu kW 0.0 0.0
Cooling Cdc (Degradation cooling)   0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25
Cooling function included Yes Yes
Heating function included Yes Yes
Average climate included Yes Yes
Cold season included No No
Warm season included No No
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.