| EWLP012KBW1N | EWLP020KBW1N | EWLP026KBW1N | EWLP030KBW1N | EWLP040KBW1N | EWLP055KBW1N | EWLP065KBW1N | ||||
|---|---|---|---|---|---|---|---|---|---|---|
| Sound power level | Cooling | Nom. | dBA | 64 | 64 | 64 | 71 | 67 | 67 | 74 |
| Refrigerant | Circuits | Quantity | 1 | 1 | 1 | 1 | 2 | 2 | 2 | |
| Control | Thermostatic expansion valve | Thermostatic expansion valve | Thermostatic expansion valve | Thermostatic expansion valve | Thermostatic expansion valve | Thermostatic expansion valve | Thermostatic expansion valve | |||
| GWP | 1,773.9 | 1,773.9 | 1,773.9 | 1,773.9 | 1,773.9 | 1,773.9 | 1,773.9 | |||
| Type | R-407C | R-407C | R-407C | R-407C | R-407C | R-407C | R-407C | |||
| Dimensions | Unit | Width | mm | 600 | 600 | 600 | 600 | 600 | 600 | 600 |
| Depth | mm | 600 | 600 | 600 | 600 | 1,200 | 1,200 | 1,200 | ||
| Height | mm | 600 | 600 | 600 | 600 | 600 | 600 | 600 | ||
| Compressor | Type | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | Hermetically sealed scroll compressor | ||
| Quantity | 1 | 1 | 1 | 1 | 2 | 2 | 2 | |||
| Weight | Unit | kg | 108 | 141 | 147 | 151 | 252 | 265 | 274 | |
| Water heat exchanger - evaporator | Water flow rate | Max. | l/min | 69 | 115 | 154 | 179 | 229 | 308 | 357 |
| Nom. | l/min | 35 | 57 | 77 | 89 | 115 | 154 | 179 | ||
| Min. | l/min | 31 | 53 | 65 | 76 | 101 | 131 | 152 | ||
| Type | Brazed plate | Brazed plate | Brazed plate | Brazed plate | Brazed plate | Brazed plate | Brazed plate | |||
| Minimum water volume in the system | l | 62 | 103 | 134 | 155 | 205 | 268 | 311 | ||
| Cooling capacity | Nom. | kW | 12.1 (1) | 20.0 (1) | 26.8 (1) | 31.2 (1) | 40.0 (1) | 53.7 (1) | 62.4 (1) | |
| EER | 2.88 (1) | 3.03 (1) | 3.15 (1) | 3.09 (1) | 2.99 (1) | 3.02 (1) | 3.07 (1) | |||
| Piping connections | Evaporator water drain | Field installation | Field installation | Field installation | Field installation | Field installation | Field installation | Field installation | ||
| Power input | Cooling | Nom. | kW | 4.2 (2) | 6.6 (2) | 8.5 (2) | 10.1 (2) | 13.4 (2) | 17.8 (2) | 20.3 (2) |
| Power supply | Phase | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | 3N~ | ||
| Name | W1 | W1 | W1 | W1 | W1 | W1 | W1 | |||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||
| Voltage | V | 400 | 400 | 400 | 400 | 400 | 400 | 400 | ||
| Notes | (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. | (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. | (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. | (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. | (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. | (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. | (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. | |||
| (2) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. This power input includes an addition for the required evaporator pump power input. | (2) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. This power input includes an addition for the required evaporator pump power input. | (2) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. This power input includes an addition for the required evaporator pump power input. | (2) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. This power input includes an addition for the required evaporator pump power input. | (2) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. This power input includes an addition for the required evaporator pump power input. | (2) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. This power input includes an addition for the required evaporator pump power input. | (2) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; condensing temp. bubble 45°C; liquid temp. 40°C; standard: Eurovent 6/C/003; condensing temp. bubble corresponds to compressor discharge pressure. This power input includes an addition for the required evaporator pump power input. | ||||
| (3) - The nominal sound power level is measured according to ISO9614 | (3) - The nominal sound power level is measured according to ISO9614 | (3) - The nominal sound power level is measured according to ISO9614 | (3) - The nominal sound power level is measured according to ISO9614 | (3) - The nominal sound power level is measured according to ISO9614 | (3) - The nominal sound power level is measured according to ISO9614 | (3) - The nominal sound power level is measured according to ISO9614 | ||||
| (4) - Its functioning relies on fluorinated greenhouse gases | (4) - Its functioning relies on fluorinated greenhouse gases | (4) - Its functioning relies on fluorinated greenhouse gases | (4) - Its functioning relies on fluorinated greenhouse gases | (4) - Its functioning relies on fluorinated greenhouse gases | (4) - Its functioning relies on fluorinated greenhouse gases | (4) - Its functioning relies on fluorinated greenhouse gases | ||||