| FXNA20A2VEB | FXNA25A2VEB | FXNA32A2VEB | FXNA40A2VEB | FXNA50A2VEB | FXNA63A2VEB | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| Cooling capacity | Total capacity | At high fan speed | kW | 2.2 | 2.8 | 3.6 | 4.5 | 5.6 | 7.1 | |
| Heating capacity | Total capacity | At high fan speed | kW | 2.5 | 3.2 | 4 | 5 | 6.3 | 8 | |
| Power input - 50Hz | Cooling | At high fan speed | kW | 0.051 | 0.051 | 0.051 | 0.069 | 0.087 | 0.108 | |
| Heating | At high fan speed | kW | 0.051 | 0.051 | 0.051 | 0.069 | 0.087 | 0.108 | ||
| Dimensions | Unit | Height | mm | 620 | 620 | 620 | 620 | 620 | 620 | |
| Width | mm | 790 | 790 | 790 | 990 | 990 | 1190 | |||
| Depth | mm | 200 | 200 | 200 | 200 | 200 | 200 | |||
| Weight | Unit | kg | 23.5 | 23.5 | 23.5 | 27.5 | 27.5 | 32 | ||
| Casing | Colour | Not painted (galvanised) | Not painted (galvanised) | Not painted (galvanised) | Not painted (galvanised) | Not painted (galvanised) | Not painted (galvanised) | |||
| Material | Galvanised steel | Galvanised steel | Galvanised steel | Galvanised steel | Galvanised steel | Galvanised steel | ||||
| Fan | Air flow rate - 50Hz | Cooling | At high fan speed | m³/min | 7.4 | 8.4 | 8.4 | 10.2 | 12.9 | 16.4 |
| At low fan speed | m³/min | 5.4 | 6.4 | 6.4 | 7.9 | 10.6 | 12.9 | |||
| External static pressure - 50Hz | High | Pa | 41 | 41 | 42 | 52 | 59 | 55 | ||
| External static pressure - 60Hz | High | Pa | 41 | 41 | 42 | 52 | 59 | 55 | ||
| Refrigerant | Type | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | |||
| GWP | 675 | 675 | 675 | 675 | 675 | 675 | ||||
| Sound power level | Cooling | At high fan speed | dBA | 49 | 51 | 52.5 | 51.5 | 55.5 | 54.5 | |
| Sound pressure level | Cooling | At high fan speed | dBA | 28 | 30 | 31.5 | 31 | 35 | 34.5 | |
| At medium fan speed | dBA | 26.5 | 28.5 | 30 | 29 | 33 | 32.5 | |||
| At low fan speed | dBA | 25 | 27 | 28.5 | 27 | 31 | 30.5 | |||
| Heating | At high fan speed | dBA | 29.5 | 31 | 33 | 32 | 36 | 35.5 | ||
| At medium fan speed | dBA | 28 | 29.5 | 31.5 | 30 | 34 | 33.5 | |||
| At low fan speed | dBA | 26.5 | 28 | 30 | 28 | 32 | 31.5 | |||
| Piping connections | Liquid | Type | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | ||
| OD | mm | 6.35 | 6.35 | 6.35 | 6.35 | 6.35 | 6.35 | |||
| Gas | Type | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | Flare connection | |||
| OD | mm | 9.52 | 9.52 | 9.52 | 12.7 | 12.7 | 12.7 | |||
| Drain | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | VP20 (I.D. 20/O.D. 26) | ||||
| Air filter | Type | Removable / washable | Removable / washable | Removable / washable | Removable / washable | Removable / washable | Removable / washable | |||
| Standard Accessories | Washer for hanger bracket | 8 | 8 | 8 | 8 | 8 | 8 | |||
| Level adjustment screw | 4 | 4 | 4 | 4 | 4 | 4 | ||||
| General safety precautions | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Clamp metal | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Drain hose | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Air filter | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Installation and operation manual | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Insulation for fitting | 2 | 2 | 2 | 2 | 2 | 2 | ||||
| Screws for duct flanges | 26 | 26 | 26 | 26 | 26 | 26 | ||||
| Sealing material | 2 | 2 | 2 | 2 | 2 | 2 | ||||
| Sealing pads | 2 | 2 | 2 | 2 | 2 | 2 | ||||
| Tie-wraps | 12 | 12 | 12 | 12 | 12 | 12 | ||||
| Washer fixing plate | 4 | 4 | 4 | 4 | 4 | 4 | ||||
| Power supply | Name | VE | VE | VE | VE | VE | VE | |||
| Phase | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | ||||
| Frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | |||
| Voltage | V | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220 | |||
| Current - 50Hz | Maximum fuse amps (MFA) | A | 6 | 6 | 6 | 6 | 6 | 6 | ||
| Notes | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | ||||
| (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | |||||
| (3) - The sound power level is an absolute value indicating the power which a sound source generates. | (3) - The sound power level is an absolute value indicating the power which a sound source generates. | (3) - The sound power level is an absolute value indicating the power which a sound source generates. | (3) - The sound power level is an absolute value indicating the power which a sound source generates. | (3) - The sound power level is an absolute value indicating the power which a sound source generates. | (3) - The sound power level is an absolute value indicating the power which a sound source generates. | |||||
| (4) - Instead of a fuse, use a circuit breaker | (4) - Instead of a fuse, use a circuit breaker | (4) - Instead of a fuse, use a circuit breaker | (4) - Instead of a fuse, use a circuit breaker | (4) - Instead of a fuse, use a circuit breaker | (4) - Instead of a fuse, use a circuit breaker | |||||
| (5) - Select wire size based on the value of MCA | (5) - Select wire size based on the value of MCA | (5) - Select wire size based on the value of MCA | (5) - Select wire size based on the value of MCA | (5) - Select wire size based on the value of MCA | (5) - Select wire size based on the value of MCA | |||||