Tableau avec les données techniques pour EWFH-TZPSD

EWFH225TZPSD1 EWFH265TZPSD1 EWFH295TZPSD1 EWFH340TZPSD1 EWFH395TZPSD1 EWFH420TZPSD1 EWFH490TZPSD1 EWFH500TZPSD2 EWFH540TZPSD2 EWFH545TZPSD1 EWFH615TZPSD2 EWFH645TZPSD2 EWFH700TZPSD2 EWFH770TZPSD2 EWFH845TZPSD2 EWFH900TZPSD2 EWFH960TZPSD2 EWFHC10TZPSD2 EWFHH10TZPSD2 EWFHH11TZPSD2 EWFHC12TZPSD2
Puissance frigorifique Nom. kW 314.39 377.84 413.94 481.12 545.38 672.02 716.4 762.26 868.15 709.3 901.97 965.07 1,058.6 1,166.75 1,227.87 1,313.47 1,373.69 1,471.78 1,527.41 1,605.75 588.19
Commande de puissance Méthode   À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance À variation continue de puissance
  Puissance minimale % 21.5 19 16.5 27.5 23 21.5 19 10 10 30 15 13.5 12.5 11.5 10.5 10 10 10 10 13.5 13.5
Puissance absorbée Rafraîchissement Nom. kW 66.38 77.51 89.54 93.35 114.38 148.22 142.4 153.37 175.31 142.95 186.01 209.12 227.02 248.93 274.14 293.71 318.72 343.47 314.15 328.91 123.39
EER 4.736 4.875 4.623 5.154 4.768 4.534 5.031 4.97 4.952 4.962 4.849 4.615 4.663 4.687 4.479 4.472 4.31 4.285 4.862 4.882 4.767
IPLV (valeur intégrée sous charge partielle) 6.738 6.736 6.579 7.506 7.214 7.271 7.135 6.819 6.956 6.73 7.347 7.226 7.016 7.052 7.143 6.966 6.615 6.787 6.825 6.965 7.041
SEER 6.008 6.095 6.081 6.58 6.397 6.579 6.481 6.199 6.24 5.753 6.646 6.55 5.945 6.46 6.506 6.388 5.929 6.3 5.568 6.031 6.095
Dimensions Unité Profondeur mm 3640 4720 4720 5800 5800 6880 6880 6880 7960 6880 7960 7960 7960 9040 10120 10120 11200 11200 12280 12280 13360
    Hauteur mm 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553 2553
    Largeur mm 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238 2238
Poids Poids en fonctionnement kg 3628 4254 4259 5,223.1 5,233.1 5,813.1 5,939.3 6391 6971 6,618.3 7900 7905 7910 8765 9329 9339 11225 11235 11797 12476 13061
  Unité kg 3307 3846 3846 4720 4720 5229 5315 5336 5846 5984 6358 6358 6358 6957 7519 7519 8341 8341 8892 9561 10070
Caisson Couleur   Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire Blanc ivoire
  Matériau   Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte Plaque en acier galvanisé peinte
Échangeur de chaleur-eau / évaporateur Type   Échangeur à plaques Échangeur à plaques Échangeur à plaques Échangeur à plaques Échangeur à plaques Échangeur à plaques Échangeur à plaques Multitubulaire Multitubulaire Échangeur à plaques Multitubulaire Multitubulaire Multitubulaire Multitubulaire Multitubulaire Multitubulaire Multitubulaire Multitubulaire Multitubulaire Multitubulaire Multitubulaire
  Volume d'eau L 40 48 48 58.1 58.1 58.1 76.3 289 289 76.3 492 492 492 583 546 546 1043 1043 1011 1011 1011
Échangeur de chaleur eau - évaporateur Échangeur de chaleur eau - évaporateur-=-Chute de pression d'eau Échangeur de chaleur eau - évaporateur-=-Chute de pression d'eau-=-Rafraîchissement Échangeur de chaleur eau - évaporateur-=-Chute de pression d'eau-=-Rafraîchissement-=-Nom.-=-kPa kPa 7.09 8.03 9.6 11.36 14.61 12.86 14.59 17.06 22.12 14.92 23.78 26.91 25.34 35.85 39.55 23.02 24.93 19.69 20.93 22.71 16.96
Échangeur de chaleur air Type   Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal Microcanal
Ventilateur Quantité   6 8 8 10 10 12 12 12 14 12 14 14 14 16 18 18 20 20 22 22 24
  Type   Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct Hélice à entraînement direct
Ventil. Débit d'air Rafraîchissement Nom. l/s 33765 45020 45020 56275 56275 67530 67530 67530 78785 67530 78785 78785 78785 90040 101295 101295 112550 112550 123805 123805 135060
Moteur de ventilateur Entraînement   Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai Sans balai
Compresseur Quantité   1 1 1 1 1 1 1 2 2 1 2 2 2 2 2 2 2 2 2 2 2
  Type   Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis Compresseur à vis
Plage de fonctionnement Côté air Rafraîchissement Min. °CBS -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20 -20
      Max. °CBS 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46 46
  Côté eau Évaporateur Min. °CBS 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
      Max. °CBS 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
Niveau de puissance sonore Rafraîchissement Nom. dBA 97.48 98.1 102.57 95.74 98.68 100.06 104.55 100.6 100.91 98.99 96.61 97.51 99.32 100.95 102.3 104.16 106.51 106.87 105.5 102.36 102.82
Niveau de pression sonore Rafraîchissement Nom. dBA 77.74 77.83 82.3 75 77.94 78.89 83.39 79.43 79.35 77.82 75.06 75.95 77.76 79.04 80.05 81.92 83.96 84.32 82.67 79.52 79.71
Réfrigérant R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze) R-1234(ze)
  Réfrigérant-=-PRP   7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7
  Charge kg 30 35 40 45 55 60 65 70 75 75 85 90 95 105 115 125 130 140 150 160 170
  Circuits Quantité   1 1 1 1 1 1 1 2 2 1 2 2 2 2 2 2 2 2 2 2 2
Raccords de tuyauterie Entrée/Sortie d'eau de l'évaporateur (DE)   88.9 88.9 88.9 139.7 139.7 139.7 139.7 168.3 168.3 139.7 219.1 219.1 219.1 219.1 219.1 219.1 273 273 273 273 273
Alimentation électrique Phase   3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
  Fréquence Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Alimentation électrique-=-Tension-=-V V 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
  Plage de tension Min. % -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    Max. % 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Unité Courant de démarrage Max. A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
  Courant de service Max. A 183 214 235 258 301 330 367 375 406 425 432 458 505 558 609 647 694 731 779 875 923
  Courant max. d’unité pour déterminer la taille des fils A 201 235 258 283 331 363 404 412 444 467 476 503 556 614 670 712 764 804 857 962 1015
Remarques (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol (1) - Cooling: EW 30°C; LW 20°C; ambient conditions: 35°CDB; 25% Ethylene glycol
  (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187 (2) - Performances referring to chiller with option 187
  (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1 (3) - Performance data calculated as Chiller Configurator - 2.2.1
  (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow. (4) - Seasonal Energy Efficiency Ratio as defined in EN14825, part load condition in cooling for Air to Water units, fan coil application, variable outlet, variable flow.
  (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition (5) - IPLV based on AHRI condition
  (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C (6) - Sound power level measured in accordance with ISO9614, referred to unit operating at Standard Rating Conditions for Air to water chillers according to EN14511:2 Outdoor Heat exchanger inlet dry bulb temperature 35°; Indoor heat exchanger inlet water temperature 12°C, outlet water temperature 7°C
  (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%. (7) - Performance referred to 400V/50Hz power supply. ±10% tolerance on Voltage, Voltage unbalance between phases must be within ± 3%.